Engineers!
Cable pulling lubricant is a critical component in properly engineered cable systems. Cable compatibility, friction reduction performance, residue combustibility, green project certification, and application method are but a few of the criteria to be considered. Don't risk your expensive cable system by leaving pulling lubricant choice to the uninformed. As explained in our free "Cable Installation Engineering" video, over 90% of cable damage occurs during installation. If you're specifying fire-retardant cable, do you really want to fill the duct with a low-tech wax-based lube, leaving a combustible track throughout your system?
Presented below are two versions of a cable lubricant specification suitable for insertion in a general electrical project specification. One is a short form, which calls out Polywater® Lubricant J as the approved lubricant. The other is the long form, which lists specific performance criteria a lube must meet for approval (real engineering!).
Please feel free to use these in your projects. You can print, save to disk, cut and paste, or contact the factory for a hardcopy. The work is already done for you. And rest assured, you'll have chosen the finest, most rigorously tested, and most commonly specified and approved cable lubricant in the world (it's cost competitive too).
Click here for the short form.
Click here for the long form.
The cable pulling lubricant shall be compatible with all cable jackets. (Excludes LSZH/LSHF cables. Use Polywater LZ instead.) The lubricant shall be UL or CSA listed. The lubricant shall contain no waxes, greases, silicones, or polyalkylene glycol oils or waxes.
A 200-gram sample of the lubricant, when placed in a one-foot, split metal conduit and fully dried for 24 hours at 105°C, shall not spread a flame more than three inches beyond a point of ignition at a continued heat flux of 40 KW/m². Total time of test shall be one-half hour.
Approved Lubricant is:
American Polywater Corporation
P.O. Box 53
Stillwater, MN 55082
(651) 430-2270
No substitutions are permitted without certification from an officer of the manufacturer that the substitute products meet all of the requirements of this specification.
The cable jacket and/or conduit walls shall be completely lubricated when cable is pulled into conduit. The lubricant shall be applied immediately before or during the pull.
Minimum quantities of lubricant are as follows:
1 Quart of Lubricant Per 100 Feet of 1-inch Conduit
2 Quarts of Lubricant Per 100 Feet of 2-inch Conduit
3 Quarts of Lubricant Per 100 Feet of 3-inch Conduit
1 Gallon of Lubricant Per 100 Feet of 4-inch Conduit
This quantity shall be increased as needed for difficult pulling situations (high temperatures, multiple bends, poor conduit condition, etc.).
The cable lubricant shall meet the following performance specs:
Approved Lubricant is:
POLYWATER® Lubricant J available from:
American Polywater Corporation
P.O. Box 53
Stillwater, MN 55082
(651) 430-2270
No substitutions are permitted without certification from an officer of the manufacturer that the substitute products meet all of the requirements of this specification.
Click here to Add Your Name To Our Mail List
Click to view the full Polywater® J Technical Data Sheet
Click here for Environmental Statement for green project certification
Click here for free Streaming Videos on cable lubrication and installation
Click here for a "Technical Talk" article on lubricant residue combustibility
Home |
About |
Site Map |
Literature |
Samples |
Links |
Reps |
Videos |
Pumps |
RFQ
Codes |
Engineering |
Shows |
Spotlight |
Newsletters |
MSDS |
Translations |
Contacts |
Jobs
11222 60th ST N | Stillwater, MN 55082-9310 USA
1-(651) 430-2270 (Voice) | 1-(651) 430-3634 (Fax)
1-(800) 328-9384 (Toll-Free US/Canada Only)
Copyright © 2001 - 2015 American Polywater Corporation | 6/5/15